How to size sump pit for rainwater if the flowrate of the water is 45l/s View All


15 years ago - 2 weeks left to answer. - 4 responses - Report Abuse
Respond to question
    0      [lnkReport]        0       0       
Share |
  Responses


Niel
When sizing a sump pump you need to know two things

1. Volume of water to be moved. You are indicating that you need to remove 45 liters per second.

2. How high you need to lift the water.

Once you know that both those things you can properly size the pump.

Please note: If there is a lot of pipe after the highest point in the system you may need to adjust the effective total lift.

The pump itself will have the correct outlet or pipe diameter to transfer that amount of water. Be sure that you do not use a smaller pipe or tube.

Niel


15 years ago

Source:


  0     0         

Azmira
ASKED BY
Thank you Niel,

The pump capacity I use is 45l/s at 15m head. To avoid pump start/stop frequently and pump will start after 4 minutes water flow in to the pit (basin). what is suitable pit (basin) size to be provided.


15 years ago

Source:


  0     0         

Niel
I miss understood your original question.

If you need to be able to handle an incoming flow rate of 45 liters / second and want wait a total of 4 minutes before the pump comes back on at full flow rate your pit will need to be big enough to handle the switch hysteresis.

In 4 minutes the in coming volume will be 45 liters x 240 seconds or nearly 11,000 liters (11 cu meters). That is a lot of water. Assuming that you float hysteresis is 10 cm the area of the pit will be 110 square meters. That is a huge sump.

What are you draining?

Niel


15 years ago

Source:


  0     0         

Azmira
ASKED BY
I'm designing sump pit for rain water at lower ground and be pumping to the discharge drain at level ground. In Malaysia our rain water intensity is very high about 200mm

14 years ago

Source:


  0     0         

ENGINEERING.com does not provide engineering advice. The Ask@ service is a forum for members to exchange ideas relating to the world of engineering. We caution users not to accept any responses that they receive without further validation, and not to rely on any engineering advice that they may get from other members of the Ask@ forum. ENGINEERING.com specifically disclaims any obligation to validate or verify any information posted within the Ask@ service. ENGINEERING.com encourages users to seek the services of a professional engineer for any engineering advice they may require.